 "design_id": "UPS-DSN-20261103-G9YQ",
 "created": "2026-11-03",
 "prices_as_of": "2026-11-03",
 "catalog": "https://ai.upstation.io/catalog.json",
 "label": "Budgetary design and estimate — not a quote",
 "customer": {
  "company": "Example AI Lab",
  "champion": "Head of ML Infrastructure",
  "decision_makers": [
   "CTO",
   "CFO"
  ],
  "criteria": [
   "time to first training run",
   "3-year cost"
  ]
 },
 "requirements": {
  "title": "4× HGX B300 training cluster (32 GPUs) with NVMe storage and a services cluster, Montana colo",
  "workload": "training",
  "gpus": 32,
  "parallelism": "multi-node",
  "storage": {
   "media": "nvme",
   "feed_gbs_per_gpu": 0.5,
   "dataset_tb": 200,
   "checkpoint_params_b": 70,
   "checkpoint_pause_s": 60,
   "checkpoints_kept": 4,
   "protection": "replica_3"
  },
  "rack_kw": 40,
  "location": "MT",
  "timeline": "production in Q2 2027",
  "services_nodes": 3
 },
 "size": {
  "gpu_class": "hgx",
  "gpu_product_id": "UPS-GPU-B300-8-T2-AIV",
  "nodes": 4,
  "gpus": 32,
  "storage": {
   "product_id": "UPS-SN-INT-NVME",
   "nodes": 5,
   "protection": "replica_3",
   "need_tb": 204.5,
   "plannable_tb": 208.3,
   "read_gbs": 16.0,
   "write_gbs": 18.7
  },
  "services": {
   "product_id": "UPS-CN-INT-1U",
   "nodes": 3
  },
  "steps": [
   "GPUs → nodes: ceil(32 ÷ 8) = 4 × 8x NVIDIA B300 (HGX B300 NVL8), Intel, 3TB (Aivres) (32 GPUs; nodes ship fully populated).",
   "Class: HGX — the GPUs must act as one (training, multi-node). Does the model at its precision fit one GPU's memory, and can each GPU work alone? Yes: PCIe. No: HGX. Distributed training is never served by PCIe servers.",
   "Storage (replica_3, Ceph across nodes, floor 3+1): plannable = 184 × N × (N−1)/N × 0.333 × 0.85; N = 5 gives 208.3 TB ≥ 204.5 TB and 5 × 20 = 100 GB/s ≥ 16.0 GB/s read.",
   "Storage demand: read = 32 × 0.5 = 16.0 GB/s; checkpoint burst = 18.7 GB/s; write = 18.7 GB/s; capacity = 204.5 TB.",
   "Cluster services (chosen with the buyer, optional): 3 × 1U CPU nodes for provisioning, scheduler and monitoring."
  ],
  "assumptions": [
   "GPU server: 8x NVIDIA B300 (HGX B300 NVL8), Intel, 3TB (Aivres) (UPS-GPU-B300-8-T2-AIV), the default HGX line (proposed)",
   "Second source: 8x NVIDIA B300 (HGX B300 NVL8), Intel (UPS-GPU-B300-8), same price and design, 30+ weeks on NVIDIA allocation. Next generation: NVIDIA Rubin (HGX Rubin NVL8, liquid-cooled racks) follows B300, not priced"
  ]
 },
 "network": {
  "fabrics": [
   {
    "role": "gpu_fabric",
    "speed": "800G",
    "switch_id": "UPS-NET-800G-32",
    "leaves": 1,
    "spines": 0,
    "oversubscription": "1:1",
    "radix": 32,
    "rails_per_leaf": null,
    "ports_used": 32,
    "ports_total": 32
   },
   {
    "role": "front_end",
    "speed": "400G",
    "switch_id": "UPS-NET-400G-32",
    "leaves": 2,
    "spines": 0,
    "oversubscription": "3:1 or better",
    "radix": 32,
    "usable": 30,
    "breakout": 4,
    "ports_used": 18,
    "ports_total": 64
   },
   {
    "role": "oob",
    "speed": "1G",
    "switch_id": "UPS-NET-1G-48",
    "leaves": 1,
    "spines": 0,
    "oversubscription": "n/a",
    "radix": 48,
    "ports_used": 15,
    "ports_total": 48
   }
  ],
  "lines": [
   {
    "role": "gpu_fabric",
    "item": "32× 800G OSFP switch (GPU fabric)",
    "unit": 37500,
    "qty": 1,
    "product_id": "UPS-NET-800G-32",
    "note": "",
    "link": null
   },
   {
    "role": "gpu_fabric",
    "item": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m — node to leaf, 1 per GPU port (estimated optical)",
    "unit": 2058,
    "qty": 32,
    "product_id": null,
    "note": "",
    "link": "gpu_node_leaf"
   },
   {
    "role": "front_end",
    "item": "32× 400G QSFP-DD switch (front-end pair, MLAG)",
    "unit": 20000,
    "qty": 2,
    "product_id": "UPS-NET-400G-32",
    "note": "",
    "link": null
   },
   {
    "role": "front_end",
    "item": "+2× 400G north-south (budgeted at the Supermicro equivalent option; Aivres fits its own 400G NICs and confirms them on its quote) (listed option, one per GPU node)",
    "unit": 2693.94,
    "qty": 4,
    "product_id": "UPS-GPU-B300-8-T2-AIV",
    "note": "option",
    "link": null
   },
   {
    "role": "front_end",
    "item": "400G AOC 10 m — GPU nodes to the pair, 2 per node",
    "unit": 1055.0,
    "qty": 8,
    "product_id": null,
    "note": "",
    "link": "fe_gpu"
   },
   {
    "role": "front_end",
    "item": "400G→4×100G breakout 2 m — storage nodes to the pair (4 nodes per cable)",
    "unit": 199.0,
    "qty": 4,
    "product_id": null,
    "note": "",
    "link": "fe_storage"
   },
   {
    "role": "front_end",
    "item": "400G→4×100G breakout 2 m — cluster services nodes to the pair (4 nodes per cable)",
    "unit": 199.0,
    "qty": 2,
    "product_id": null,
    "note": "",
    "link": "fe_services"
   },
   {
    "role": "front_end",
    "item": "400G 2 m passive DAC — peer link",
    "unit": 174.0,
    "qty": 2,
    "product_id": null,
    "note": "",
    "link": "fe_peer"
   },
   {
    "role": "oob",
    "item": "48× 1G RJ45 + 4× 10G switch (OOB)",
    "unit": 989,
    "qty": 1,
    "product_id": "UPS-NET-1G-48",
    "note": "",
    "link": null
   },
   {
    "role": "oob",
    "item": "Cat6 patch — 1G BMC/management (not priced)",
    "unit": 0,
    "qty": 15,
    "product_id": null,
    "note": "",
    "link": "oob"
   }
  ],
  "steps": [
   "GPU fabric: 32 × 800G ports (1 per GPU) ≤ 32 → one 32× 800G OSFP switch, 1:1 non-blocking (single point of failure; a leaf-spine removes it).",
   "Front-end: 2 ports per host, one to each switch of an MLAG pair of 32× 400G QSFP-DD switches; 7 ports per switch of 30 usable → 1 pair(s). Storage stays converged on this plane (well under 40 GB/s per node).",
   "OOB: 12 hosts + 3 switches = 15 × 1G ports → 1 × 48× 1G RJ45 + 4× 10G."
  ],
  "assumptions": [],
  "mermaid": "flowchart TB\n  GF[\"GPU fabric: 1× 32× 800G OSFP<br/>800G 1:1, 32 links\"]\n  GN[\"4× 8x NVIDIA B300 (HGX B300 NVL8)\"] -- \"32× 800G\" --> GF\n  FE[\"Front-end MLAG pair: 2× 32× 400G QSFP-DD<br/>400G, storage converged\"]\n  GN -- \"2× 400G per node\" --> FE\n  SN[\"5× 2U all-NVMe storage node\"] -- \"2× 100G per node\" --> FE\n  MG[\"3× cluster services node\"] -- \"2 ports per node\" --> FE\n  FE -. \"uplinks to your core (not priced)\" .-> CORE((\"Your network\"))\n  OOB[\"OOB: 1× 1G switch\"] -. \"BMC, 15 ports\" .- GN",
  "port_map": [
   {
    "fabric": "gpu_fabric",
    "a": "gpu-01",
    "a_port": "GPU NIC 1",
    "b": "gpu-sw-1",
    "b_port": "1",
    "cable_id": "C0001",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-01",
    "a_port": "GPU NIC 2",
    "b": "gpu-sw-1",
    "b_port": "2",
    "cable_id": "C0002",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-01",
    "a_port": "GPU NIC 3",
    "b": "gpu-sw-1",
    "b_port": "3",
    "cable_id": "C0003",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-01",
    "a_port": "GPU NIC 4",
    "b": "gpu-sw-1",
    "b_port": "4",
    "cable_id": "C0004",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-01",
    "a_port": "GPU NIC 5",
    "b": "gpu-sw-1",
    "b_port": "5",
    "cable_id": "C0005",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-01",
    "a_port": "GPU NIC 6",
    "b": "gpu-sw-1",
    "b_port": "6",
    "cable_id": "C0006",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-01",
    "a_port": "GPU NIC 7",
    "b": "gpu-sw-1",
    "b_port": "7",
    "cable_id": "C0007",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-01",
    "a_port": "GPU NIC 8",
    "b": "gpu-sw-1",
    "b_port": "8",
    "cable_id": "C0008",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-02",
    "a_port": "GPU NIC 1",
    "b": "gpu-sw-1",
    "b_port": "9",
    "cable_id": "C0009",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-02",
    "a_port": "GPU NIC 2",
    "b": "gpu-sw-1",
    "b_port": "10",
    "cable_id": "C0010",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-02",
    "a_port": "GPU NIC 3",
    "b": "gpu-sw-1",
    "b_port": "11",
    "cable_id": "C0011",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-02",
    "a_port": "GPU NIC 4",
    "b": "gpu-sw-1",
    "b_port": "12",
    "cable_id": "C0012",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-02",
    "a_port": "GPU NIC 5",
    "b": "gpu-sw-1",
    "b_port": "13",
    "cable_id": "C0013",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-02",
    "a_port": "GPU NIC 6",
    "b": "gpu-sw-1",
    "b_port": "14",
    "cable_id": "C0014",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-02",
    "a_port": "GPU NIC 7",
    "b": "gpu-sw-1",
    "b_port": "15",
    "cable_id": "C0015",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-02",
    "a_port": "GPU NIC 8",
    "b": "gpu-sw-1",
    "b_port": "16",
    "cable_id": "C0016",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-03",
    "a_port": "GPU NIC 1",
    "b": "gpu-sw-1",
    "b_port": "17",
    "cable_id": "C0017",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-03",
    "a_port": "GPU NIC 2",
    "b": "gpu-sw-1",
    "b_port": "18",
    "cable_id": "C0018",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-03",
    "a_port": "GPU NIC 3",
    "b": "gpu-sw-1",
    "b_port": "19",
    "cable_id": "C0019",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-03",
    "a_port": "GPU NIC 4",
    "b": "gpu-sw-1",
    "b_port": "20",
    "cable_id": "C0020",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-03",
    "a_port": "GPU NIC 5",
    "b": "gpu-sw-1",
    "b_port": "21",
    "cable_id": "C0021",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-03",
    "a_port": "GPU NIC 6",
    "b": "gpu-sw-1",
    "b_port": "22",
    "cable_id": "C0022",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-03",
    "a_port": "GPU NIC 7",
    "b": "gpu-sw-1",
    "b_port": "23",
    "cable_id": "C0023",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-03",
    "a_port": "GPU NIC 8",
    "b": "gpu-sw-1",
    "b_port": "24",
    "cable_id": "C0024",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-04",
    "a_port": "GPU NIC 1",
    "b": "gpu-sw-1",
    "b_port": "25",
    "cable_id": "C0025",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-04",
    "a_port": "GPU NIC 2",
    "b": "gpu-sw-1",
    "b_port": "26",
    "cable_id": "C0026",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-04",
    "a_port": "GPU NIC 3",
    "b": "gpu-sw-1",
    "b_port": "27",
    "cable_id": "C0027",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-04",
    "a_port": "GPU NIC 4",
    "b": "gpu-sw-1",
    "b_port": "28",
    "cable_id": "C0028",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-04",
    "a_port": "GPU NIC 5",
    "b": "gpu-sw-1",
    "b_port": "29",
    "cable_id": "C0029",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-04",
    "a_port": "GPU NIC 6",
    "b": "gpu-sw-1",
    "b_port": "30",
    "cable_id": "C0030",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-04",
    "a_port": "GPU NIC 7",
    "b": "gpu-sw-1",
    "b_port": "31",
    "cable_id": "C0031",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "gpu_fabric",
    "a": "gpu-04",
    "a_port": "GPU NIC 8",
    "b": "gpu-sw-1",
    "b_port": "32",
    "cable_id": "C0032",
    "cable": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m",
    "link": "gpu_node_leaf"
   },
   {
    "fabric": "front_end",
    "a": "gpu-01",
    "a_port": "FE 1",
    "b": "fe-1a",
    "b_port": "1",
    "cable_id": "C0033",
    "cable": "400G AOC 10 m",
    "link": "fe_gpu"
   },
   {
    "fabric": "front_end",
    "a": "gpu-01",
    "a_port": "FE 2",
    "b": "fe-1b",
    "b_port": "1",
    "cable_id": "C0034",
    "cable": "400G AOC 10 m",
    "link": "fe_gpu"
   },
   {
    "fabric": "front_end",
    "a": "gpu-02",
    "a_port": "FE 1",
    "b": "fe-1a",
    "b_port": "2",
    "cable_id": "C0035",
    "cable": "400G AOC 10 m",
    "link": "fe_gpu"
   },
   {
    "fabric": "front_end",
    "a": "gpu-02",
    "a_port": "FE 2",
    "b": "fe-1b",
    "b_port": "2",
    "cable_id": "C0036",
    "cable": "400G AOC 10 m",
    "link": "fe_gpu"
   },
   {
    "fabric": "front_end",
    "a": "gpu-03",
    "a_port": "FE 1",
    "b": "fe-1a",
    "b_port": "3",
    "cable_id": "C0037",
    "cable": "400G AOC 10 m",
    "link": "fe_gpu"
   },
   {
    "fabric": "front_end",
    "a": "gpu-03",
    "a_port": "FE 2",
    "b": "fe-1b",
    "b_port": "3",
    "cable_id": "C0038",
    "cable": "400G AOC 10 m",
    "link": "fe_gpu"
   },
   {
    "fabric": "front_end",
    "a": "gpu-04",
    "a_port": "FE 1",
    "b": "fe-1a",
    "b_port": "4",
    "cable_id": "C0039",
    "cable": "400G AOC 10 m",
    "link": "fe_gpu"
   },
   {
    "fabric": "front_end",
    "a": "gpu-04",
    "a_port": "FE 2",
    "b": "fe-1b",
    "b_port": "4",
    "cable_id": "C0040",
    "cable": "400G AOC 10 m",
    "link": "fe_gpu"
   },
   {
    "fabric": "front_end",
    "a": "stor-01",
    "a_port": "FE 1",
    "b": "fe-1a",
    "b_port": "5/1",
    "cable_id": "C0041",
    "cable": "400G→4×100G breakout 2 m",
    "link": "fe_storage"
   },
   {
    "fabric": "front_end",
    "a": "stor-01",
    "a_port": "FE 2",
    "b": "fe-1b",
    "b_port": "5/1",
    "cable_id": "C0042",
    "cable": "400G→4×100G breakout 2 m",
    "link": "fe_storage"
   },
   {
    "fabric": "front_end",
    "a": "stor-02",
    "a_port": "FE 1",
    "b": "fe-1a",
    "b_port": "5/2",
    "cable_id": "C0041",
    "cable": "400G→4×100G breakout 2 m",
    "link": "fe_storage"
   },
   {
    "fabric": "front_end",
    "a": "stor-02",
    "a_port": "FE 2",
    "b": "fe-1b",
    "b_port": "5/2",
    "cable_id": "C0042",
    "cable": "400G→4×100G breakout 2 m",
    "link": "fe_storage"
   },
   {
    "fabric": "front_end",
    "a": "stor-03",
    "a_port": "FE 1",
    "b": "fe-1a",
    "b_port": "5/3",
    "cable_id": "C0041",
    "cable": "400G→4×100G breakout 2 m",
    "link": "fe_storage"
   },
   {
    "fabric": "front_end",
    "a": "stor-03",
    "a_port": "FE 2",
    "b": "fe-1b",
    "b_port": "5/3",
    "cable_id": "C0042",
    "cable": "400G→4×100G breakout 2 m",
    "link": "fe_storage"
   },
   {
    "fabric": "front_end",
    "a": "stor-04",
    "a_port": "FE 1",
    "b": "fe-1a",
    "b_port": "5/4",
    "cable_id": "C0041",
    "cable": "400G→4×100G breakout 2 m",
    "link": "fe_storage"
   },
   {
    "fabric": "front_end",
    "a": "stor-04",
    "a_port": "FE 2",
    "b": "fe-1b",
    "b_port": "5/4",
    "cable_id": "C0042",
    "cable": "400G→4×100G breakout 2 m",
    "link": "fe_storage"
   },
   {
    "fabric": "front_end",
    "a": "stor-05",
    "a_port": "FE 1",
    "b": "fe-1a",
    "b_port": "6/1",
    "cable_id": "C0043",
    "cable": "400G→4×100G breakout 2 m",
    "link": "fe_storage"
   },
   {
    "fabric": "front_end",
    "a": "stor-05",
    "a_port": "FE 2",
    "b": "fe-1b",
    "b_port": "6/1",
    "cable_id": "C0044",
    "cable": "400G→4×100G breakout 2 m",
    "link": "fe_storage"
   },
   {
    "fabric": "front_end",
    "a": "svc-01",
    "a_port": "FE 1",
    "b": "fe-1a",
    "b_port": "7/1",
    "cable_id": "C0045",
    "cable": "400G→4×100G breakout 2 m",
    "link": "fe_services"
   },
   {
    "fabric": "front_end",
    "a": "svc-01",
    "a_port": "FE 2",
    "b": "fe-1b",
    "b_port": "7/1",
    "cable_id": "C0046",
    "cable": "400G→4×100G breakout 2 m",
    "link": "fe_services"
   },
   {
    "fabric": "front_end",
    "a": "svc-02",
    "a_port": "FE 1",
    "b": "fe-1a",
    "b_port": "7/2",
    "cable_id": "C0045",
    "cable": "400G→4×100G breakout 2 m",
    "link": "fe_services"
   },
   {
    "fabric": "front_end",
    "a": "svc-02",
    "a_port": "FE 2",
    "b": "fe-1b",
    "b_port": "7/2",
    "cable_id": "C0046",
    "cable": "400G→4×100G breakout 2 m",
    "link": "fe_services"
   },
   {
    "fabric": "front_end",
    "a": "svc-03",
    "a_port": "FE 1",
    "b": "fe-1a",
    "b_port": "7/3",
    "cable_id": "C0045",
    "cable": "400G→4×100G breakout 2 m",
    "link": "fe_services"
   },
   {
    "fabric": "front_end",
    "a": "svc-03",
    "a_port": "FE 2",
    "b": "fe-1b",
    "b_port": "7/3",
    "cable_id": "C0046",
    "cable": "400G→4×100G breakout 2 m",
    "link": "fe_services"
   },
   {
    "fabric": "front_end",
    "a": "fe-1a",
    "a_port": "31",
    "b": "fe-1b",
    "b_port": "31",
    "cable_id": "C0047",
    "cable": "400G 2 m passive DAC",
    "link": "fe_peer"
   },
   {
    "fabric": "front_end",
    "a": "fe-1a",
    "a_port": "32",
    "b": "fe-1b",
    "b_port": "32",
    "cable_id": "C0048",
    "cable": "400G 2 m passive DAC",
    "link": "fe_peer"
   },
   {
    "fabric": "oob",
    "a": "gpu-01",
    "a_port": "BMC",
    "b": "oob-1",
    "b_port": "1",
    "cable_id": "C0049",
    "cable": "Cat6 patch",
    "link": "oob"
   },
   {
    "fabric": "oob",
    "a": "gpu-02",
    "a_port": "BMC",
    "b": "oob-1",
    "b_port": "2",
    "cable_id": "C0050",
    "cable": "Cat6 patch",
    "link": "oob"
   },
   {
    "fabric": "oob",
    "a": "gpu-03",
    "a_port": "BMC",
    "b": "oob-1",
    "b_port": "3",
    "cable_id": "C0051",
    "cable": "Cat6 patch",
    "link": "oob"
   },
   {
    "fabric": "oob",
    "a": "gpu-04",
    "a_port": "BMC",
    "b": "oob-1",
    "b_port": "4",
    "cable_id": "C0052",
    "cable": "Cat6 patch",
    "link": "oob"
   },
   {
    "fabric": "oob",
    "a": "stor-01",
    "a_port": "BMC",
    "b": "oob-1",
    "b_port": "5",
    "cable_id": "C0053",
    "cable": "Cat6 patch",
    "link": "oob"
   },
   {
    "fabric": "oob",
    "a": "stor-02",
    "a_port": "BMC",
    "b": "oob-1",
    "b_port": "6",
    "cable_id": "C0054",
    "cable": "Cat6 patch",
    "link": "oob"
   },
   {
    "fabric": "oob",
    "a": "stor-03",
    "a_port": "BMC",
    "b": "oob-1",
    "b_port": "7",
    "cable_id": "C0055",
    "cable": "Cat6 patch",
    "link": "oob"
   },
   {
    "fabric": "oob",
    "a": "stor-04",
    "a_port": "BMC",
    "b": "oob-1",
    "b_port": "8",
    "cable_id": "C0056",
    "cable": "Cat6 patch",
    "link": "oob"
   },
   {
    "fabric": "oob",
    "a": "stor-05",
    "a_port": "BMC",
    "b": "oob-1",
    "b_port": "9",
    "cable_id": "C0057",
    "cable": "Cat6 patch",
    "link": "oob"
   },
   {
    "fabric": "oob",
    "a": "svc-01",
    "a_port": "BMC",
    "b": "oob-1",
    "b_port": "10",
    "cable_id": "C0058",
    "cable": "Cat6 patch",
    "link": "oob"
   },
   {
    "fabric": "oob",
    "a": "svc-02",
    "a_port": "BMC",
    "b": "oob-1",
    "b_port": "11",
    "cable_id": "C0059",
    "cable": "Cat6 patch",
    "link": "oob"
   },
   {
    "fabric": "oob",
    "a": "svc-03",
    "a_port": "BMC",
    "b": "oob-1",
    "b_port": "12",
    "cable_id": "C0060",
    "cable": "Cat6 patch",
    "link": "oob"
   },
   {
    "fabric": "oob",
    "a": "gpu-sw-1",
    "a_port": "mgmt",
    "b": "oob-1",
    "b_port": "13",
    "cable_id": "C0061",
    "cable": "Cat6 patch",
    "link": "oob"
   },
   {
    "fabric": "oob",
    "a": "fe-1a",
    "a_port": "mgmt",
    "b": "oob-1",
    "b_port": "14",
    "cable_id": "C0062",
    "cable": "Cat6 patch",
    "link": "oob"
   },
   {
    "fabric": "oob",
    "a": "fe-1b",
    "a_port": "mgmt",
    "b": "oob-1",
    "b_port": "15",
    "cable_id": "C0063",
    "cable": "Cat6 patch",
    "link": "oob"
   }
  ]
 },
 "racks": {
  "rack_kw": 40,
  "usable_u": 40,
  "racks": [
   {
    "name": "Compute 1",
    "devices": [
     {
      "role": "gpu_node",
      "name": "gpu-01",
      "product_id": "UPS-GPU-B300-8-T2-AIV",
      "label": "8x NVIDIA B300 (HGX B300 NVL8)",
      "ru": 10,
      "kw": 16.96,
      "psu": 6,
      "u": 1
     },
     {
      "role": "gpu_node",
      "name": "gpu-02",
      "product_id": "UPS-GPU-B300-8-T2-AIV",
      "label": "8x NVIDIA B300 (HGX B300 NVL8)",
      "ru": 10,
      "kw": 16.96,
      "psu": 6,
      "u": 11
     },
     {
      "role": "gpu_fabric",
      "name": "gpu-sw-1",
      "product_id": "UPS-NET-800G-32",
      "label": "32× 800G OSFP switch — GPU fabric",
      "ru": 1,
      "kw": 1.25,
      "psu": 2,
      "u": 40
     },
     {
      "role": "oob",
      "name": "oob-1",
      "product_id": "UPS-NET-1G-48",
      "label": "48× 1G RJ45 + 4× 10G switch — OOB",
      "ru": 1,
      "kw": 0.07,
      "psu": 2,
      "u": 39
     }
    ],
    "u_used": 22,
    "kw": 35.24,
    "circuit": "415V 3-ph 60A",
    "circuit_rated_kw": 43.116,
    "circuit_pairs": 1,
    "feeds": "A+B, each carries the whole rack",
    "feed_load_pct": 82,
    "outlets_per_feed": 8
   },
   {
    "name": "Compute 2",
    "devices": [
     {
      "role": "gpu_node",
      "name": "gpu-03",
      "product_id": "UPS-GPU-B300-8-T2-AIV",
      "label": "8x NVIDIA B300 (HGX B300 NVL8)",
      "ru": 10,
      "kw": 16.96,
      "psu": 6,
      "u": 1
     },
     {
      "role": "gpu_node",
      "name": "gpu-04",
      "product_id": "UPS-GPU-B300-8-T2-AIV",
      "label": "8x NVIDIA B300 (HGX B300 NVL8)",
      "ru": 10,
      "kw": 16.96,
      "psu": 6,
      "u": 11
     }
    ],
    "u_used": 20,
    "kw": 33.92,
    "circuit": "415V 3-ph 60A",
    "circuit_rated_kw": 43.116,
    "circuit_pairs": 1,
    "feeds": "A+B, each carries the whole rack",
    "feed_load_pct": 79,
    "outlets_per_feed": 6
   },
   {
    "name": "Services 1",
    "devices": [
     {
      "role": "front_end",
      "name": "fe-1a",
      "product_id": "UPS-NET-400G-32",
      "label": "32× 400G QSFP-DD switch — front-end pair, MLAG",
      "ru": 1,
      "kw": 0.75,
      "psu": 2,
      "u": 40
     },
     {
      "role": "front_end",
      "name": "fe-1b",
      "product_id": "UPS-NET-400G-32",
      "label": "32× 400G QSFP-DD switch — front-end pair, MLAG",
      "ru": 1,
      "kw": 0.75,
      "psu": 2,
      "u": 39
     },
     {
      "role": "storage_node",
      "name": "stor-01",
      "product_id": "UPS-SN-INT-NVME",
      "label": "2U all-NVMe storage node",
      "ru": 2,
      "kw": 1.65,
      "psu": 2,
      "u": 1
     },
     {
      "role": "storage_node",
      "name": "stor-02",
      "product_id": "UPS-SN-INT-NVME",
      "label": "2U all-NVMe storage node",
      "ru": 2,
      "kw": 1.65,
      "psu": 2,
      "u": 3
     },
     {
      "role": "storage_node",
      "name": "stor-03",
      "product_id": "UPS-SN-INT-NVME",
      "label": "2U all-NVMe storage node",
      "ru": 2,
      "kw": 1.65,
      "psu": 2,
      "u": 5
     },
     {
      "role": "storage_node",
      "name": "stor-04",
      "product_id": "UPS-SN-INT-NVME",
      "label": "2U all-NVMe storage node",
      "ru": 2,
      "kw": 1.65,
      "psu": 2,
      "u": 7
     },
     {
      "role": "storage_node",
      "name": "stor-05",
      "product_id": "UPS-SN-INT-NVME",
      "label": "2U all-NVMe storage node",
      "ru": 2,
      "kw": 1.65,
      "psu": 2,
      "u": 9
     },
     {
      "role": "services_node",
      "name": "svc-01",
      "product_id": "UPS-CN-INT-1U",
      "label": "1U compute node",
      "ru": 1,
      "kw": 1.2,
      "psu": 2,
      "u": 11
     },
     {
      "role": "services_node",
      "name": "svc-02",
      "product_id": "UPS-CN-INT-1U",
      "label": "1U compute node",
      "ru": 1,
      "kw": 1.2,
      "psu": 2,
      "u": 12
     },
     {
      "role": "services_node",
      "name": "svc-03",
      "product_id": "UPS-CN-INT-1U",
      "label": "1U compute node",
      "ru": 1,
      "kw": 1.2,
      "psu": 2,
      "u": 13
     }
    ],
    "u_used": 15,
    "kw": 13.35,
    "circuit": "208V 3-ph 50A",
    "circuit_rated_kw": 18.0,
    "circuit_pairs": 1,
    "feeds": "A+B, each carries the whole rack",
    "feed_load_pct": 74,
    "outlets_per_feed": 10
   }
  ],
  "provision_kw": 82.51,
  "steps": [
   "GPU nodes per 40 kW rack = min(floor(40 U ÷ 10 U), floor(40 ÷ 16.96 kW)) = 2 (power binds).",
   "Compute 1: 22 U, 35.24 kW provisioned → 1 × 415V 3-ph 60A circuit pair (A+B), 82% of each feed; 8 power cords per feed.",
   "Compute 2: 20 U, 33.92 kW provisioned → 1 × 415V 3-ph 60A circuit pair (A+B), 79% of each feed; 6 power cords per feed.",
   "Services 1: 15 U, 13.35 kW provisioned → 1 × 208V 3-ph 50A circuit pair (A+B), 74% of each feed; 10 power cords per feed."
  ],
  "colo_options": [
   {
    "key": "MT",
    "location": "Montana",
    "rate_usd_per_kw_month": 260,
    "usd_per_month": 21453,
    "term_months": 36,
    "term_total": 772308,
    "sales_tax": "none",
    "property_tax": "none on the first $1M of equipment, about 0.8%/yr above"
   },
   {
    "key": "TX",
    "location": "Texas",
    "rate_usd_per_kw_month": 225,
    "usd_per_month": 18565,
    "term_months": 36,
    "term_total": 668340,
    "sales_tax": "8.25% (6.25% state + local); the data-center exemption needs $200M and 20 jobs",
    "property_tax": "about 2.2%/yr of market value"
   },
   {
    "key": "OR",
    "location": "Oregon",
    "rate_usd_per_kw_month": 175,
    "usd_per_month": 14439,
    "term_months": 36,
    "term_total": 519804,
    "sales_tax": "none",
    "property_tax": "about 1.5-2%/yr of market value (ORS 308.290); abatements closed to data-center property since 2026"
   },
   {
    "key": "PA",
    "location": "Pennsylvania",
    "rate_usd_per_kw_month": 250,
    "usd_per_month": 20628,
    "term_months": 36,
    "term_total": 742608,
    "sales_tax": "6% (8% Philadelphia, 7% Allegheny), or none if the facility is state-certified and the tenant holds its own exemption certificate (100 kW+, 2-year contract) before buying",
    "property_tax": "none"
   },
   {
    "key": "CA",
    "location": "Canada (Ontario, Quebec)",
    "rate_usd_per_kw_month": 225,
    "usd_per_month": 18565,
    "term_months": 36,
    "term_total": 668340,
    "sales_tax": "HST 13% (Ontario) or GST+QST (Quebec) on hardware and colo, recovered as an input tax credit by a registered business",
    "property_tax": "none"
   }
  ],
  "colo": {
   "location": "Montana",
   "key": "MT",
   "rate_usd_per_kw_month": 260,
   "term_months": 36,
   "usd_per_month": 21453,
   "internet": null,
   "internet_usd_per_month": null
  }
 },
 "estimate": {
  "lines": [
   {
    "section": "GPU servers",
    "product_id": "UPS-GPU-B300-8-T2-AIV",
    "url": "https://ai.upstation.io/p/UPS-GPU-B300-8-T2-AIV",
    "item": "8x NVIDIA B300 (HGX B300 NVL8), Intel, 3TB (Aivres) — Aivres KR9288X3",
    "unit": 537196.4,
    "qty": 4,
    "extended": 2148785.6,
    "basis": "priced as the Supermicro HGX B300 equivalent (UPS-GPU-B300-8; interchangeable): eStore B2B net, 12% off list",
    "approx": false,
    "lead_time": "Configure-to-order on Aivres B300 allocation (October 2026 schedule): the Intel build is Aivres's lead B300 through February 2027, with new orders delivering from mid-to-late January 2027 in limited quantities and larger lots January-March 2027; GPU supply confirmed per project, and once the allocation is used, 30+ weeks. Est. 11-20 weeks",
    "lead_weeks": 20
   },
   {
    "section": "Storage",
    "product_id": "UPS-SN-INT-NVME",
    "url": "https://ai.upstation.io/p/UPS-SN-INT-NVME",
    "item": "2U all-NVMe storage node, dual socket, 24x 7.68TB NVMe (184TB raw) — SYS-222C-TN",
    "unit": 177958.91,
    "qty": 5,
    "extended": 889794.55,
    "basis": "eStore B2B net, 12% off list",
    "approx": false,
    "lead_time": "Barebone in stock (2026-11-03); configure-to-order. Est. 3-5 weeks",
    "lead_weeks": 5
   },
   {
    "section": "Cluster services",
    "product_id": "UPS-CN-INT-1U",
    "url": "https://ai.upstation.io/p/UPS-CN-INT-1U",
    "item": "1U compute node, dual socket, 64 cores, 512GB, diskless NVMe (virtualisation host) — SYS-122C-TN",
    "unit": 34523.31,
    "qty": 3,
    "extended": 103569.93,
    "basis": "eStore B2B net, 12% off list",
    "approx": false,
    "lead_time": "Barebone in stock (2026-11-03); configure-to-order. Est. 3-5 weeks",
    "lead_weeks": 5
   },
   {
    "section": "GPU fabric",
    "product_id": "UPS-NET-800G-32",
    "url": "https://ai.upstation.io/p/UPS-NET-800G-32",
    "item": "32× 800G OSFP switch (GPU fabric) — FS N8650-32OD, PicOS",
    "unit": 37500,
    "qty": 1,
    "extended": 37500,
    "basis": "vendor public price",
    "approx": false,
    "lead_time": "26 in stock (global warehouse, 2026-11-03). ~1 week",
    "lead_weeks": 1
   },
   {
    "section": "GPU fabric cabling",
    "product_id": null,
    "url": "https://ai.upstation.io/switches",
    "item": "800G link: 2× SR8 + 2× MTP-12 OM4 10 m — node to leaf, 1 per GPU port (estimated optical)",
    "unit": 2058,
    "qty": 32,
    "extended": 65856,
    "basis": "FS.com public price, generic-coded",
    "approx": false,
    "lead_time": null,
    "lead_weeks": null
   },
   {
    "section": "Front-end network",
    "product_id": "UPS-NET-400G-32",
    "url": "https://ai.upstation.io/p/UPS-NET-400G-32",
    "item": "32× 400G QSFP-DD switch (front-end pair, MLAG) — FS N8610-32D, PicOS",
    "unit": 20000,
    "qty": 2,
    "extended": 40000,
    "basis": "vendor public price",
    "approx": false,
    "lead_time": "33 in stock (global warehouse, 2026-11-03). ~1 week",
    "lead_weeks": 1
   },
   {
    "section": "Front-end network",
    "product_id": "UPS-GPU-B300-8-T2-AIV",
    "url": "https://ai.upstation.io/p/UPS-GPU-B300-8-T2-AIV",
    "item": "+2× 400G north-south (budgeted at the Supermicro equivalent option; Aivres fits its own 400G NICs and confirms them on its quote) (listed option, one per GPU node)",
    "unit": 2693.94,
    "qty": 4,
    "extended": 10775.76,
    "basis": "priced as the Supermicro HGX B300 equivalent (UPS-GPU-B300-8; interchangeable): eStore B2B net, 12% off list",
    "approx": false,
    "lead_time": null,
    "lead_weeks": null
   },
   {
    "section": "Front-end network cabling",
    "product_id": null,
    "url": "https://ai.upstation.io/switches",
    "item": "400G AOC 10 m — GPU nodes to the pair, 2 per node",
    "unit": 1055.0,
    "qty": 8,
    "extended": 8440.0,
    "basis": "FS.com public price, generic-coded",
    "approx": false,
    "lead_time": null,
    "lead_weeks": null
   },
   {
    "section": "Front-end network cabling",
    "product_id": null,
    "url": "https://ai.upstation.io/switches",
    "item": "400G→4×100G breakout 2 m — storage nodes to the pair (4 nodes per cable)",
    "unit": 199.0,
    "qty": 4,
    "extended": 796.0,
    "basis": "FS.com public price, generic-coded",
    "approx": false,
    "lead_time": null,
    "lead_weeks": null
   },
   {
    "section": "Front-end network cabling",
    "product_id": null,
    "url": "https://ai.upstation.io/switches",
    "item": "400G→4×100G breakout 2 m — cluster services nodes to the pair (4 nodes per cable)",
    "unit": 199.0,
    "qty": 2,
    "extended": 398.0,
    "basis": "FS.com public price, generic-coded",
    "approx": false,
    "lead_time": null,
    "lead_weeks": null
   },
   {
    "section": "Front-end network cabling",
    "product_id": null,
    "url": "https://ai.upstation.io/switches",
    "item": "400G 2 m passive DAC — peer link",
    "unit": 174.0,
    "qty": 2,
    "extended": 348.0,
    "basis": "FS.com public price, generic-coded",
    "approx": false,
    "lead_time": null,
    "lead_weeks": null
   },
   {
    "section": "Out-of-band",
    "product_id": "UPS-NET-1G-48",
    "url": "https://ai.upstation.io/p/UPS-NET-1G-48",
    "item": "48× 1G RJ45 + 4× 10G switch (OOB) — FS S3410-48TS, PicOS",
    "unit": 989,
    "qty": 1,
    "extended": 989,
    "basis": "vendor public price",
    "approx": false,
    "lead_time": "593 in stock (global warehouse, 2026-11-03). ~1 week",
    "lead_weeks": 1
   }
  ],
  "capex": 3307252.84,
  "opex_per_month": 21453,
  "year_one": 3564688.84,
  "tco_3y": 4079560.84,
  "tco_5y": 4594432.84,
  "longest_lead_weeks": 20,
  "lead_driver": "8x NVIDIA B300 (HGX B300 NVL8), Intel, 3TB (Aivres) — Aivres KR9288X3",
  "dated_leads": [],
  "excluded": [
   "Racks, PDUs, whips and cabling labour",
   "Uplinks to the buyer's core network",
   "Software (cluster manager, storage software), unless listed",
   "Taxes, shipping and duties",
   "Installation and on-site services"
  ]
 },
 "assumptions": [
  "GPU server: 8x NVIDIA B300 (HGX B300 NVL8), Intel, 3TB (Aivres) (UPS-GPU-B300-8-T2-AIV), the default HGX line (proposed)",
  "Second source: 8x NVIDIA B300 (HGX B300 NVL8), Intel (UPS-GPU-B300-8), same price and design, 30+ weeks on NVIDIA allocation. Next generation: NVIDIA Rubin (HGX Rubin NVL8, liquid-cooled racks) follows B300, not priced"
 ],
 "next_step": "Book the intro (https://calendly.com/alecglover/intro-call) or email alec@upstation.io with the design ID; UpStation validates the design and introduces the supplier that fits.",
 "title": "4× HGX B300 training cluster (32 GPUs) with NVMe storage and a services cluster, Montana colo",
 "summary": "4× 8x NVIDIA B300 (HGX B300 NVL8) (32 GPUs, HGX class), 5× 2U all-NVMe storage node storage (208.3 TB plannable, replica_3), 3 cluster services nodes. Networks: gpu fabric 800G on 1 switch; front end 400G on 2 switches; oob 1G on 1 switch. 3 racks at ≤ 40 kW, 82.51 kW provisioned, in Montana colo. Every figure is computed from the ai.upstation.io catalog with the arithmetic shown below."
}